Lawn and open ground
450 mm (18 in) is the minimum cover for direct-buried conduit; most installations sit at 600–750 mm to stay clear of landscaping and shallow digging.
How deep to bury conduit
Direct-buried electrical conduit is normally installed at a minimum depth of 450 mm (18 in) below finished grade, with typical installations at 600–750 mm. Where the run crosses a driveway, yard or road surface, cover rises to 750 mm, and a full road crossing is often detailed at 900 mm. Everything else — the locate request, the hand-dig zone, the backfill layers — follows from getting that first number right.
This guide is not the legal code for your plot, not a contractor's quotation, and not a substitute for the locate marks on the ground.
Scroll the strip sideways — 6 cards.
450 mm (18 in) is the minimum cover for direct-buried conduit; most installations sit at 600–750 mm to stay clear of landscaping and shallow digging.
Where the run passes under a driveway, yard or road surface, cover normally increases to 750 mm (30 in) to carry wheel loads.
A crossing under a carriageway is often detailed at 900 mm, keeping the duct clear of resurfacing plant and heavy axles.
Within 300 mm (UK) to 600 mm (US) either side of a marked line, mechanical digging is barred and the line is exposed by hand.
Sand or fine granular material, particles no larger than 40 mm, placed by hand above the duct before any excavated soil returns.
Frost penetrates 750–1500 mm in cold continental climates and near zero in tropical ground, so the depth rule cannot be copied between them.
Three pages, three questions
Direct-buried conduit needs at least 450 mm (18 in) of cover below finished grade, with typical installations at 600–750 mm.
Cover is the vertical distance from the finished surface down to the top of the conduit or duct. It is not the same as trench depth: the trench must also make room for bedding and surround below and around the pipe, so the dig is always deeper than the cover figure suggests.
The 450 mm figure is the floor, not the target. Most specifications land at 600–750 mm for direct-buried runs because that band keeps the duct clear of shallow landscaping, fence posts and surface digging while staying cheap to excavate.
Two forces push the figure deeper: what travels over the surface, and how far frost penetrates the ground. Both are treated in their own sections below, and either can override the baseline.
| Where the run sits | Cover below finished grade | What sets the figure |
|---|---|---|
| Open lawn or unpaved ground | 450 mm (18 in) minimum | Baseline rule for direct-buried conduit |
| Typical direct-buried installation | 600–750 mm | Keeps clear of landscaping and shallow digging |
| Driveway, yard or road-surface crossing | 750 mm (30 in) | Wheel loads and resurfacing plant |
| Full road crossing | 900 mm | Heavier axle loads and carriageway planing |
| Telecom polymer duct | 500–900 mm | Laid deeper than power; no fault current if cracked |
| Cold continental climate | 750–1500 mm | Frost penetration governs the deep end |
| Tropical ground | Frost allowance near zero | Surface rules govern; baseline depths apply |
Each sketch shows cover measured from finished grade to the top of the duct, with the surround and backfill layers in place.